20AG01 Tank#1 Agitator 11 480 1 0.7 1 0.7 7.7 15LT03 Lighting transformer 15 480 1 0.5 1 0.5 7.5 20PU21 Tank #1 Supply pump 30 480 1 0.8 1 0.8 24 20PU22 Tank #1 Supply pump 30 480 0 0.8 1 0.5 0 15FA11 Crusher building fan 30 480 1 0.6 1 0.6 18 15CR01 Crusher building crane 50 480 1 0.4 0.1 0.05 2.5 21BM01 Ball mill 2000 4160 1 0.7 0.6 0.7 840 21BM02 Ball mill 2000 4160 1 0.7 0.6 0.7 840 15WR01 Welding receptacle 60 480 1 0.5 0.1 0.05 3.0 Connected 4226 Operating 1742.7

      Abbreviations: ID, identification number; kW, connected load; Serv., unit in service (1) or on standby (0); LF, load factor (<1); UF, utilization factor (<1); DF, calculated diversity factor (Serv *LF*UF).

      Occasionally, it does happen that a motor is undersized and must be replaced. But, more often, the motors are oversized and operate with a low load factor. That scenario does not seem to concern the owners. Falling short certainly is a bad news.

      Based on the small sample, the operating load is 41.2% of the connected total load. This is just an engineering guess on the paper, for now.

      One can create his own tabulation to suit the particular plant and define the load factors for its own reasonable comfort suited to a type of the plant. In this case, we used the factors for the peaking duty: peaking operation for one hour duration. The load in the table is calculated by multiplying the connected load (kW) with the diversity factor (DF).

      Based on the load estimate for the 4.16 kV load, the plant transformers will be 13.2 to 4.16 kV, 12/15 MVA, Dyn1, ONAN/ONAF, BIL 110 kV, 55 °C rise at 30 or 40 °C ambient, depending on the environment. If the plant is in the Northern region, the ambient temperature can be <40 °C.

      For the primary distribution, we can apply either 13.8 or 20, or even 33 kV voltages. The switching equipment and cables at 20 and 33 kV are considerably more expensive compared to 13.8 kV equipment. However, higher voltages may be needed if the distances are over 10 km and if there is a need for transfer of larger blocks of power. Since the project requires a large number of short feeders, it does not seem to be cost‐effective to distribute minor load at higher voltages.

      The distances to the plant load centers are not large (<6 km) and 13.8 kV can be employed without significant voltage drops (<5%), which is to be verified by system studies.

      Therefore, 13.8 kV voltage seems to be the most appropriate for the primary distribution throughout the site for this 40 MVA plant.

Photo of a primary switchgear located at the main substation several kilometers away from the process plant with convenient routes to feed all the plant buildings with overhead distribution lines.