voltage at PCC has to be regulated to a reference voltage. The battery is supposed to supply active or reactive power to the grid to maintain the PCC voltage. The current reference ( (id(ref), iq(ref)) is obtained from an outer voltage loop. The outer voltage loop ensures that the PCC voltage is maintained at its reference value. The modeling of the converter and design of the controller under different modes is discussed in the next section.

       2.5.2.1 Modelling and Control of the VSI

      The AC voltage of the PCC is expressed as

      (2.21)image

      Applying Kirchhoff ’s voltage equation in the phase, we get

      (2.22)image

      (2.23)image

      To transfer the above system to synchronous reference frame, the following transformation need to be performed

      (2.25)image

      Where Tabc2αβ, Tαβ2dq and θ are known as Clark transformation, Park transformation, and the phase angle of the grid which is obtained from PLL, respectively. The resulting system after transformation is given by

      Where vsd, ud and id are PCC voltage, VSC output voltage and output current on d-axis, respectively. uq and iq are VSC output voltage and output current on the q-axis, respectively. One can notice from equation (2.26) and (2.27) that the system is converted to an LTI system having some coupling states. A simple control law to decouple the term is given by

      (2.28)image

      Where vid and viq are the feedback control input. for obtaining zero steady-state error, PI controller is applied to control input

      For the case when the microgrid in islanded mode, the converter has to regulate the voltage at PCC. By applying Kirchhoff’s law at the PCC voltage and applying the d-q transform on the resulting equations, one would obtain

      (2.30)image

      The coupling between Vsd and V sq is eliminated by a decoupling feed-forward compensation. One possible control law is given by

      (2.31)image

      Where id(ref), iq(ref) are reference for inner current loop and vvd, and vv are the feedback control input which is expressed as

      (2.32)image

      Where evd = (Vsd ( ref )Vsd), evq = (Vsq(ref)Vsq), Kpv,d, Kiv,d, Kpv,q, and Kiv,q are parameters/gains of PI controller for d-axis current and q-axis voltage controller. The parameter of PI controller can be easily selected. For d-q transformation in islanded system, the reference angle ρ (and thus image) is decided independently.

       2.5.2.3 Typical Case Study in MATLAB-Simulink

      (2.33)image

      (2.34)image

Parameter Value
Nominal voltage (VB) 700 V
Rated capacity 150 Ah
Initial SOC 60%
inverter side inductance (L) and ESR (rL) of inductor 1mH, 0.005Ω
Filter capacitor (Cf) 20 µF
AC load PL=1000 W QL =100 VAR
AC microgrid voltage (Vphase(rms)) grid side inductance Lg 220 V300 µH

      Where P is the rated output active power of one phase for three-phase full-bridge inverter, Vg is the phase voltage, Vdc is the dc link voltage fsw is switching frequency, Ka = 0.2, image

      The control is implemented in the Simulink platform. The commands “Modecommand” along with the power to be exchanged (Pref, Qref), with microgird are sent to the controller from the EMS of the microgrid. The feedback signals PCC voltage (Vsx), inverter current (iLx), grid voltage (Vgx) are also input to the controller.