Power Flow Control Solutions for a Modern Grid Using SMART Power Flow Controllers. Kalyan K. Sen. Читать онлайн. Newlib. NEWLIB.NET

Автор: Kalyan K. Sen
Издательство: John Wiley & Sons Limited
Серия:
Жанр произведения: Физика
Год издания: 0
isbn: 9781119824381
Скачать книгу

      where the magnitude of the voltage (Vs′) at the modified sending end is Vs′ and the corresponding phase angle is δs′,

      and the modified power angle is given by

      (2‐62)equation

      (2‐81)equation

      and

      (2‐82a)equation

      Therefore, a simultaneous regulation of the magnitude ( Vs′ ) and the modified power angle ( δ′ ) of the line voltage is needed for an independent control of active and reactive power flows in the line.

      The transfer of power flow from one line to another can be achieved with the use of a BTB‐STATCOM that consists of at least two VSCs, each of which is connected in shunt (parallel) with the transmission line through a coupling transformer. All the VSCs are connected at their common DC link. The shunt‐compensating voltage is of variable magnitude and phase angle, and it is also at any phase angle with the prevailing line current. Accordingly, it exchanges active and reactive powers with the line. The exchanged active power by one VSC flows bidirectionally through the common DC link to another VSC. Each shunt‐connected VSC can also provide an independent shunt reactive power compensation at its AC terminal and, thereby, regulates the voltage at the POC. Each shunt‐connected VSC is rated for the full line voltage and carries the full line current and, therefore, is rated for its full transmitted power. As an example, in order to increase the power flow in a line from its natural flow of 800 MVA to 1000 MVA, the rating of each of the two units of the Shunt–Shunt Compensator would be 1000 MVA. In some special cases for point‐to‐point transfer of power between two isolated networks with different voltages, phase angles, or frequencies, the use of the Shunt–Shunt Compensator may be the preferred solution.

      The Shunt–Shunt Compensator may also be implemented, using a common electromechanical or magnetic link in which case, the compensating voltage is generated from either an electrical machine or a transformer with LTCs. In the case of a magnetic link, both active and reactive powers flow through the link. The point‐to‐point transfer of power from one line to another with different voltages, phase angles, or frequencies can be accomplished with the use of shunt–shunt‐connected electrical machines. The Sen Transformer can also generate a shunt‐compensating voltage for the interconnection of two nearby grids with different voltages and phase angles, but the frequencies of the two grids must be the same.

Schematic illustration of ranges of Qr versus Pr at the receiving end of the transmission line.

      In an alternate approach to the Shunt–Shunt compensation, the same active and reactive power flows (Pr and Qr) can be obtained using a PFC with a Shunt–Series configuration that applies a series‐compensating voltage (images), such that

      (2‐94b)equation

      or when δs = 0°,

equation

      where the phase‐shift angle,

       (2‐51b) equation

      or

      The magnitude (Vs′s) and the relative phase angle (β) of the series‐compensating voltage (Vs′s) are

      (2‐100)equation

      and

      (2‐101)equation

      For a Shunt–Shunt Compensator, the relationship between the active and reactive power flows (Pr and Qr) at the receiving end is shown by a quarter