cabling and purposes. For instance, establish that cable C1 for all the plant motors is always the cable from the motor starter going to PLC. If that cable is not used, that number is skipped for that particular drive. Push button station always occupies cable C2, etc. This consistent method of numbering will help you computerize the cable lists and to sort the lists to specific equipment.

      The equipment numbers are needed to create load lists, which will later be expanded to create the list of schematics and cable lists. For instance by adding to the list of loads: the load names, voltage, kW rating, MCC, and bucket, a computer program can create a list of cables, select the cable sizes, and assign “From – To” destinations without any manual input.

      If you add a typical schematic diagram type for each drive or feeder to the load list, the computer program will assign and fill in the cables and cable details on the drawings for each particular drive/feeder without any human input.

      Adopt minimum cable sizes: #12 American wire gauge (AWG) for power and #16 AWG for controls.

      Should the kW rating change and a new kW rating be entered into the list, the cable size will be computer‐updated automatically when the cable list is regenerated.

      The same computer program generates and prints the schematic and wiring diagrams automatically adding to the drawing of all the specific data including the cable data, input/output (I/O) data, and wiring terminations.

ID Name Volt kW MCC In service Type
40 PU 003 Feed Pump, Water Tank 1 460 15 MCC11 1 T1
40 PU 004 Feed Pump, Water Tank 1 460 15 MCC11 SB T1
30 AG 006 Agitator, Tank 6 460 10 MCC03 1 T1
30 CR 001 Crane, 60 Tone, Main Hall 460 100 MCC03 1 F1
10 RF 003 Crusher Roof Fan 460 1 MCC 01 1 T3

      In service: 1 = operating, SB = on standby.

      Type: this is the designation of the type of operating circuit to be implemented.

Cable ID Cable size kW Type/class From To Length
40 PU 003 P 1‐3/c #10 AWG, 20 Teck 600V MCC11 PU Motor 120
40 PU 003 C1 1‐5/c #16 AWG, Teck 300V MCC11 PLC 2 15
40 PU 003 C2 1‐3/c #14 AWG, Teck 300V MCC11 PB Stn 120
40 PU 004 P 1‐3/c #10AWG, 20 Teck 600V MCC11 PU Motor 120
40 PU 004 C1 1‐5/c #16 AWG, Teck 300V MCC11 PLC 2 15
40 PU 004 C2 1‐3/c #14 AWG, Teck 300V MCC11 PBStn 120
40 PU 004 C3 1‐2/c #14 AWG, Teck 300V MCC11 TH1 130
30 AG 005 P 1‐3/c #12AWG, 15 Teck 600V MCC05 PU Motor 85
30 AG 005 C1 1‐5/c #16 AWG, Teck 300V MCC05 PLC 3 20
30 AG 005 C2 1‐3/c #14 AWG, Teck 300V MCC05 PB Stn 85
10 SP 003 P 1‐3/c # 12 AWG, 5 Teck 600V MCC01 PU Motor 60
10 SP 003 C2